1. Using the PowerWorld Simulator, create three input data files: bus input data, line input data, and transformer input data as shown in Figure 4. Note that bus 1 is the swing bus. Your output for this part consists of three power-flow input data files. 2. Run the power flow program and obtain the bus, line, and transformer input/output data files that you prepared in Part 1. 3. The Bus voltage magnitude should be between 0.98 < V < 1.03 per unit at all buses during both light and heavy loads. Find two settings for the compensation, one for light and one for heavy loads. Hint: Use Shunt Compensation.Case 1: Normal condition Case 2: Light Load Condition (60%) Case 3: Heavy Load Condition (120%) along with a one-paragraph explanation of your methods for increasing/decreasing the voltage at all buses within the range. 4. Compute subtransient fault currents for a bolted three-phase-to-ground fault at bus 2, 5 ,6, and transmission line L5-6. Also compute bus voltages during the faults and the positive- sequence bus impedance matrix. Assume 1.0 per-unit prefault voltage. Neglect prefault load currents and all losses. Your output for this part consists of three input data files and three output data (fault currents, bus voltages, and the bus impedance matrix) files. 5. Compute sub-transient fault currents for (1) single-line-to-ground, (2) line-to-line, and (3) double line-to-ground bolted faults at bus 2, 5 ,6 and transmission line L5-6. Also compute the zero-, positive-, and negative-sequence bus impedance matrices. Assume 1.0 per-unit prefault voltage. Also, neglect prefault load currents and all losses. 6. By using this simulator, the user can determine whether the given system can still operate under an acceptable state in certain contingencies. Assume the bus voltages should be maintained within +10% of the rated voltage. Investigate whether the system will remain secure: 1. When the transmission line between buses 4 and 6 is out of service. 2. When the transmission line between buses 2 and 5 is out of service. 3. When the transformer between buses 3 and 4 is out of service. 4. When the Generator at bus 1 is out of service
Question